CG SERIES AC GROUND CONTINUITY TESTER

Specifications:

Measuring Resistance Rang

0~0.1 omh / 0~0.5 omh
Measuring Accuracy 3A~5A +/- 10% of full scale; 5A~30A +/- 5% of full scale
Test Current Output AC3~30A
Test Voltage Max output Voltage 8V AC Typically
Resistance Meter Indicate the testing Resistance and setting value of FALL and OFFSET.
Current Meter Indicate the testing Current and setting value of warring
Switching Zero-Cross Solid-Sate
Warning Test

1. A Warning alarm is sounded when the test current value shifts by more than roughly +/- 10%
2. The prescribed value can be set to any range of 3~30A.

Offset

1. Offset range :UP to 0.1
2. Offset error : Max +/- 5% of full scale

Hi Limit

1. Measuring range can be set between 5~100%
2. +/-15% of full scale with respect to reference value(3~5A)
3. +/-10% of full scale with respect to reference value(5~30A)

Timer 1S,10S,1Min,10Min,4range.
Remote Control

PIN5/PIN2 short stop controlling
PIN4/PIN2 short start controlling
PIN1 out:+24V 20mA,PIN2 GND,PIN3NC

Test Mode  normal:

If the warning acted then the test will stop.

Test Mode continue: If the warning acted then the test will be continuously
Buzzer Alarm A Buzzer is sounded when the test fail acted.
Test Frequency 50Hz or 60Hz independent by line voltage.
Output Single TEST, PASS, FAIL, WARNING, READY, MONITOR
Power Source 115V/230V +/- 10% 1 Ø 50/60Hz.
Standard Accessories Instruction manual x1, Test Lead CG503-1x1,Power cordx1
Dimensions 430x145x415(mm)(WxHxD)
Weight Approx:18.5KG

¡@

  Consult the Factory The Customer Specification.

  Specifications Subject to Change Without Notice.

¡@