LISN-2-16 Line Impedance Stabilization Networks
 
 

Contact

2-Line V-LISN; Acc. to CISPR16-1 Spec

 
-
Frequencyrange9kHz¡V30MHz
-
Impedance50£[//50£gH+5£[
-
Insertionloss<2.0dB
-
Highpassfilter150kHz(connectible)5pol.,Chebycheff
-
Limiter136dB£gV(connectible)
-
Attenuator20dB/2W(connectible)
-
PE-Simulation50£gH/16air-corecoil(connectible
-
Powerrating2x16A(230V)
-
RemoteTTL-Level
-
Incl.Correctionvalues
-
Incl.CertificateofConformity

Application

Within the range of the line-bounded interfering voltage measurement technique, the standard CISPR-16-1 demands measuring instruments which are simulating a reproducible impedance of the mains supply and are blocking disturbances out of the mains. Is a frequency range of 9 kHz to 30 MHz existing, a so-called LISN is required with a defined developing of impedance.

Solution

For this purpose MTS Systemtechnik has developed a LISN which fulfills the requirements of the CISPR 16-1. This LISN has 2 phases with a maximum ampacity of 2x16A.

Characteristics

-
LISN according to CISPR, EN, VDE, ANSI - Operating voltage switchable (115/ 230V)
-
Frequency range 9 kHz to 30 MHz - 19"-Table top case
- Test connection through protection conductor socket - Remote controlable over TTL-levels
- International style (G, GB, F, I, CH, USA) - Permanent current up to 2x 16A
- Air-core coil - Calibrated according to CISPR 16-1:1999
- Small insertion loss