LISN-4-250 Line Impedance Stabilization Networks
 
 

Contact

4-Line V-LISN; Acc. to CISPR16-1 Spec

 
-
Frequencyrange150kHz¡V30MHz
-
IImpedance50£gH//50£[
-
IInsertionloss<2.0dB
-
Limiter140dB£gV(fixed)
-
Attenuator20dB/2W(fixed)
-
Operatingvoltage115/200VAC(DC-63Hz);230/400VAC(DC-63Hz)
-
Powerrating4x250A
-
Auxiliarycurrentsupply115/230V¡V60VAswitchable
-
RemoteTTL-Level
-
IIncl.Correctionvalues
-
Incl.CertificateofConformity

Application

Within the range of the line-bounded interfering voltage measurement technique, the standard CISPR-16-1 demands measuring instruments which are simulating a reproducible impedance of the mains supply and are blocking disturbances out of the mains. Is a frequency range of 150 kHz to 30 MHz existing, a so-called LISN is required with a defined developing of impedance.

Solution

For this purpose MTS Systemtechnik has developed a LISN which fulfills the requirements of the CISPR 16-1. This LISN has 4 phases with a maximum ampacity of 4x 250A.

Characteristics

-
LISN according to CISPR, EN, VDE, ANSI - Temperature control
-
Frequency range 150 kHz to 30 MHz - Integrated cooling
- Permanent current up to 4x 250 A - Remote controlable over TTL-levels
- Contact-voltage-proof high current connections - Calibrated according to CISPR 16-1:1999
- Air-core coil    
- Small insertion loss