| Computing Functions: |
| Function | Apparent Power (VA) | Reactive Power (Var) | Power Factor (PF) | Phase Angle (DEG) |
| Computation | VxA | ((VA)2-W2)^(1/2) | W/V.A | COS-1| PF| |
| Range | VA Range | VA Range | 0 to 1 | 0 to +/- 90 |
| Display | 19999 | 19999 | +/- 1.0000 | +/- 90.00 |
| Accuracy | +/- 0.001% of VA range | +/- 0.001% of VA range | +/- 0.0001 | PF error +/-0.01 |
|
Total
Harmonic Distortiion (THD) CP-660-2 CP-660-5 |
Ranges (Auto) | 10%. 100% | ||
| Display resolution | 4 digits (0.001% ~ 99.99%) | |||
| Frequency Range (Automatic Tuned) | 45Hz ~ 65Hz. 370Hz ~ 430Hz | |||
| Crest Factors | Up to 3 | |||
| Fundamental Rejection | 80db and above | |||
| Residual DIstortion and noise | Less than 0.1% (Sine Wave) | |||
|
Detection
Type (THD-R) (THD-F=THD-R/¡Ô(1-(THD-R)2) , bandwidth=5KHz |
True
RMS F: Fundamental Frequency |
|||
| Measuring Input | Voltage or Current | |||
|
Frequency (Hz) |
Ranges (Auto 4 Range) | 100Hz. 1kHz. 10kHz. 100kHz | ||
| Display Resolution / Maximmum resolution | 5 digits / 0.001Hz | |||
| Operating Principle | Reciprocal Counting method | |||
| Accuracy (23oC +/-5oC) | +/- 0.01% +/-1C | |||
| Measuring Input | Voltage or Current | |||
|
Peak
Voltage (+pk) (-pk) (P-P) |
Ranges (Auto or Manual) (7 Range) | CP-600-2 CP-660-2 | +/- 0.6A 1.5A 3A 6A 15A 30A 60A (CP-620-2) | |
| CP-600-5 CP-660-5 | +/- 1.5A 3A 6A 15A 30A 60A 150A | |||
| Display Resolution | 4-1/2 digits | |||
| Frequency Range | 10Hz to 100kHz | |||
| Accuracy | +/- 1% reading +/- 1%range +/- 1%/KHz | |||
|
Crest
Factor (CF) |
Ranges | 1.000 to 9.999 | ||
| Frequency Range | 10Hz to 100kHz | |||
| Accuracy | +/- 1%reading +/- 1%range +/- 1%/KHz | |||
| Measuring Input | Voltage or Current | |||
|
Inrush
Current (Ins) |
Ranges (7 Range / Int shunt) | 60mA to 60Apk(20A)/150mA to 150A peak(50A) | ||
| Accuracy | +/- 3% of selected range | |||
|
Integrator (INTG) |
Function | Wh. VAh. VArh. Ah | ||
| DIsplay Resoultion | 6 digits (Max 999.999M) | |||
| Unit | m.K.M | |||
| Integration Interval | 0.3second | |||
| Elapsed Time Display | 5 digits 1 minute to 999 hours 59 minute | |||
| Timer accuracy | +/- 0.01% | |||
|
Interfaces (Optional) |
GPIB | Specifications | Standard IEEEE 488.2 | |
| Function | SH1 AH1 T6 L4 SR1 PL1 PP0 DC1 DT1 C0 | |||
| RS-232 | Mode | Start stop synchronization | ||
| Baud rate | 1200. 2400. 4800. 9600bps | |||
| Print Port | Specifications | Standard Centronics (IBM-PC Compatible) | ||
| Driver | EPSON LQ Series and Compatible | |||
| Print Interval | 1 second to 24 Hurs(1 second STEP) | |||
| Print Count | 1~9999 | |||
| Print Format | Panel display or All Parameter | |||
| Environment | Temperature | Operating | 0oC to 50oC | |
| Storage | -40oC to + 70oC | |||
| Humidity | 10% to 90% RH non-condensing | |||
| Dielectric Strength | Inputs to Case or Power supply | 2kV AC 50/60Hz for 1 minute | ||
| Power Supply to Case | 1.5kV AC 50/60Hz for 1 minute | |||
¡@
|
|